Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W525 Combined analogue input/output module with galvanic isolationInput/output (I/O) modules5
Configuration
Module connections/LED
The connections of the module terminal are the following:Description of the LED:
● Off: Module is not powered. Uext (24 V) is missing.
● On: Module is running without errors
● Blinking slow: Channel error (Over range/under range/short circuit/open load)
● Blinking fast: Uext is lower than specified (< 19 V)
How to configure the inputs
Each input channel is configured by a DIP-Switch with four switches. The function of
each switch is the following:Switch nr. Off On
1
2
3
4Differential ModeGain=1Single Ended Mode
Current Shunt On
Supply for external Resistors On
Gain=0.25According to this table, the configuration for the different modes of operation is as fol-
lows:Voltage mode
0...10 VCurrent mode
0...20 mA
4...20 mATemperature mode
Pt1000 (-50...400 ̊C)
Pt500 (-50...400 ̊C)
Ni1000 (-60...200 ̊C)
Resistor mode
0...2500 ΩHow to configure the outputs
Since the outputs are configured by software (with the corresponding FBox or FB),
there is no need to configure the mode of operation of the outputs with any kind of
jumpers or DIP-Switches.