Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Saia-Burgess Controls AG


PCD2.W6x0

Input/output (I/O) modules

5


Changing the jumpers
There are components on this circuit board, that are sensitive to electrostatic discharges.
For further information, refer to Appendix B, “Icons”.

Range selection (PCD2.W610)
Jumpers, factory settings: A0 ... A3:A3: “V” “V” (voltage)(voltage)
U/B: “B” (bipolar)
Reset select: “mid“ (reset to mid-scale,
i.e. 0 V in bipolar mode)
Ranges depending on application:
Per module: U/B: Unipolar or Bipolar operation
Reset select:Reset select:Reset select: Reset toReset toReset to low- or mid-scale
Rec. setting:Rec. setting: Unipolar →low-scaleUnipolar →low-scale→low-scalelow-scale
Bipolar → mid-scale→ mid-scale mid-scale
Per channel: “V” Voltage output:
0 ... +10 V or -10 V ... +10 V
“C”: Current output: 0 ... 20 mA

Current outputs have been laid out for unipolar mode. Bipolar mode is possible, but
for the negative half of this operation the output is 0 mA.

Connection concept
Connection for 0 ... 10 V or -10 V ... +10 V: (selectable on the PCD2.W610)

4 (A2)


D
A

5 U
R≥ 3 kΩ

Connection for 0 ... 20 mA: (PCD2.W610 only)

4 (A2)


D

A

5 I

+ 24 VDC


R = 0.. 500 Ω


Contrôle de la
tension de la
source de
courant

An external 24 VDC supply is required for current outputs.