Hardware Manual

(John Hannent) #1

Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Saia-Burgess Controls AG


PCD2.H100

Input/output (I/O) modules

5


5.15.1 PCD2.H100, counting module up to 20 kHz


Application
Simple counting module, comprising two inputs “A” and “B” plus one direct control
output marked “CCO”; allows counting of the number of revolutions or the calculation
of distances (pulses) and the measurement by counting of pulses within a logical
AND gate (second input).

Typical areas of application:
● Counting revolutions or distances (impulses)
● Presetting a count value and switching off output CCO when Counter = 0
● Measurement by counting: measuring signals counted only when particular
conditions are met, e.g. photoelectric barrier covered
● Counting with recognition of count direction for incremental shaft encoders
providing simple motion control

Technical data

Number of systems: 1
Counting range: 0 ... 65,535 (16 bit) (can be extended with CPU counters)
Counting frequency: max. 20 kHz (at pulse/pause ratio 50 %)
Data protection: All data in this module are volatile
(non-volatile PCD registers are available).
Digital inputs
“IN-A” and “IN-B” signal voltages: nominal voltage: 24 V24 VDC
“low” range: -30...+5 V-30 ... +5 V
“high” range: +15...30 V for source operation+15 ... 30 V for source operationfor source operation
Input current: typically 7.5 mA
Input filer: 25 kHz
Process output
Counter controlled output CCO: counter output (switches when count is 0 or 65,535) (switches when count is 0 or 65,535)(switches when count is 0 or 65,535)
Current range: 5 ... 500 mA (max. current leakage 1 mA)
(min. load resistance 48(min. load resistance 48 48 �� in voltage�� in voltage�� in voltage voltagevoltage
range 5...24 V).range 5 ... 24 V).).
Voltage range: 5 ... 32 V smoothed, residual ripple max. 10 %residual ripple max. 10 %
Circuit type: Electrically coupled, not short circuit protected,
positive switching
Voltage drop: typically 2V at 500 mA
Output delay: < 10 μs, (longer for inductive load due to
protective diode).
Power supply
External supply 5 ... 32 VDC, (for supply of CCO output only)for supply of CCO output only)
Internal current consumption:
(from +5 V bus)from +5 V bus)

max. 90 mA

Internal current consumption:
(from V+ bus)

0 mA

External current consumption: CCO output load current
Operational conditions
Ambient temperature operation: 0 ... +55 °C without forced ventilation,
storage: -20...+85 °C-20...+85 °C-20 ... +85 °C
Noise immunity: EC mark according to EN 61 000-6-3 and EN 61 000-6-2