Hardware Manual

(John Hannent) #1

Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Saia-Burgess Controls AG


PCD2.H110

Input/output (I/O) modules

5


5.15.2 PCD2.H110, general purpose counting / measuring module up to 100 kHzgeneral purpose counting / measuring module up to 100 kHz


Application
Measuring and fast counting module for general counting and simple motion control
tasks; also for specific applications such as frequency measurement, period and
pulse length measurement, etc. The module is equipped with an FPGA (Field
Programmable Gate Array) and can be programmed for special high volume
applications by using a plug-in PROM.
Technical data

Number of systems: 1
Counting range: 0 ... 16,777,215 (24 bit)
Counting frequency: up to 100 kHz
Data protection: All data in this module are volatile
(non-volatile PCD registers are available).
Digital inputs
Number of inputs:
Terminal 0 = E0
Terminal 1 = E1
Terminal 2 = E2
Terminal 3 = E3

4


Input “A”: for counting and measuring
Input “B”: for counting only
Input “Enable C”: for use as counting module
Input “Enable M”: for use as measuring modulefor use as measuring module
Nominal voltage: 24 VDC
“low” range: -30 ... +5 V
“high” range: +15...30 V for source operation+15 ... 30 V for source operationfor source operation
Input current: typically 6.5 mA
Input filer: 150 kHz
Circuit type: electrically connected
Digital outputs
Number of outputs:
Terminal 4 A0:
Terminal 5 A1:

2


Output “CCO” (for counter)
Output “TCO” (for measuring functions)
Current range: 5 ... 500 mA (max. current leakage 1 mA)
(min. load resistance 48(min. load resistance 48 48 �� in voltage �� in voltage�� in voltage
range 5 ... 24 V).).
Frequency: ≤ 100 kHz
Voltage range: 5 ... 32 V smoothed, residual ripple max. 10 %residual ripple max. 10 %
Circuit type: Electrically coupled, not short circuit protected,
positive switching
Voltage drop: typically < 0.5 V at 500 mA
Output delay: < 1 μs, (longer for inductive load due to
protective diode).
Power supply
External supply 5 ... 32 VDC, (for supply of CCO output only)for supply of CCO output only)
Internal current consumption:
(from +5 V bus)from +5 V bus)

max. 90 mA

Internal current consumption:
(from V+ bus)

0 mA

External current consumption: max. 2 A (all outputs)
Operational conditions
Ambient temperature operation: 0 ... +55 °C without forced ventilation,
storage: -20...+85 °C-20...+85 °C-20 ... +85 °C
Noise immunity: EC mark according to EN 61 000-6-3 and EN 61 000-6-2
Programming: Based on PCD user program and pre-programmed
function blocks (FB).