Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
Backup of the user program
CPUs and expansion housings
3
Restoring a text/DB, SYSWR K 9001
Instruction: SYSWR K 90011)
K number ; address of the texts/DBs as
; K constant or in a
; register, existing text/DB addresses in
; the range >= 4000 mAy be used
1) Alternatively, the value 9001 can be passed in a register. On the PCD3, the instruction
SYSWR K 3001 is used for the same function. For reasons of compatibility, SYSWR K
3001 can also be used on the PCD1/2, but this alternative was only integrated into the
firmware in the 2nd half of 2004
Accu status after execution:
low: the text/DB has been restored and the process is
complete, so further SYSWR K 900x instructions can be
executed immediately
high: the last instruction has not yet processed to completion;
before further SYSWR K 900x instructions, a SYSRD
K 9000 must be executed to check the readiness of the
flash card
When using the instruction SYSWR K 9001, note the following:
A SYSRD K 9000 must be executed before this instruction, to test whether the
flash card is available and ready
If errors occur during processing, e.g. because no flash card is plugged in, XOB 13
will be invoked (where present), or the Error LED will be set