Communication interfaces

4


4 PCD Classic communication interfaces


Saia® S-Net, the networking concept from Saia-Burgess Controls, is based on the
RS 485, Profibus and Ethernet open standards. Ethernet covers layers 1 and 2 of the
ISO layer model. Based on layer 2, a variety of different protocols and applications
can be run in parallel on the same network.

For PCD2.M480 only:
Layer 2 (Field Data Link-FDL) from Profibus also allows parallel running of different
application protocols such as DP, FMS and others. The use of this facility allows
Profi S-Net to be used to create a “Private Control Network (PCN)”. This makes all
Saia® units into active network components.
Profibus Layer 2 (FDL) is integrated into the operating system of the PCD2.M480
CPUs, giving these units a Profi S-Net connection with transmission speeds up to
1.5 Mbps.
These units support Profibus DP and S-Net on the same port. In this way, Profibus
can be used to construct networks cheaply and flexibly (detailed notes can be found
in TI 26 / 381).

Transmission rates (Baud rates) of the PCD2.M480:
The controllers of the type PCD2.M480 have a new Saia® NT operating system. With
the new operating system higher transmission rates (Saia® S-Bus up to 115 kBit / s)
can be achieved, however low baud rates (300 and 600 Baud / sec.) are no more sup-
ported.