204 THREE-PHASE CIRCUITS AND RESIDENTIAL WIRING
ZB
Y–∆ transformation
For the balanced case,
A ZAB
C
B
ZA
ZC
ZAB =
ZAZB + ZBZC + ZCZA
ZC
ZBC =
ZAZB + ZBZC + ZCZA
ZA
ZCA =ZAZB^ +^ ZBZC^ +^ ZCZA
ZB
ZAB = ZBC = ZCA = Z∆ = 3 ZY
∆–Y transformation
For the balanced case,
1
3
ZA =
ZABZCA
ZAB + ZBC + ZCA
ZB =
ZABZBC
ZAB + ZBC + ZCA
ZC =
ZCAZBC
ZAB + ZBC + ZCA
ZA = ZB = ZC = ZY = Z∆
ZCA
ZBC
Figure 4.2.1Wye–delta and delta–wye transformations.
angle (20° in our example). The load power factor is given by cos 20° for our problem, and it is
said to belaggingin this case, as the impedance angle is positive and the phase current lags the
corresponding phase voltage by that angle.
The problem can also be solved in a simpler way by making use of a single-line equivalent
circuit, as shown in Figure 4.2.2.(c),
I ̄L=
V ̄L−N
Z ̄ =
( 208 /
√
3 )0°
10 20°
= 12 −20° (4.2.5)
in whichV ̄L−Nis chosen as the reference for convenience. The magnitude of the line current
and the power factor angle are known; the negative sign associated with the angle indicates that
the power factor is lagging. By knowing that the line (or phase) currentsI ̄A, I ̄B, I ̄Clag their
respective voltagesV ̄AN,V ̄BN, andV ̄CNby 20°, the phase angles of various voltages and currents,
if desired, can be obtained with respect to any chosen reference, such asV ̄BC.
Balanced Delta-Connected Load
Next, let us consider the case of a balanced delta-connected load with impedance of 5 45°
supplied by a three-phase, three-wire 100-V system, as shown in Figure 4.2.3(a). We shall
determine the line currents and draw the corresponding phasor diagram.
With the assumed positive phase sequence (A–B–C) and withV ̄BCas the reference phasor,
the line-to-line voltagesV ̄AB, V ̄BC, andV ̄CAare shown in Figure 4.2.3. The rms value of the
line-to-line voltages is 100 V for our example. Choosing the positive directions of the line and
phase currents as in Figure 4.2.3(a), we have
I ̄AB=
V ̄AB
Z ̄ =
100 120°
5 45°
= 20 75° (4.2.6)
I ̄BC=
V ̄BC
Z ̄
=
100 0°
5 45°
= 20 −45° (4.2.7)
I ̄CA=
V ̄CA
Z ̄ =
100 240°
5 45°
= 20 195° (4.2.8)
By the application of Kirchhoff’s current law at each of the vertices of the delta-connected
load, we obtain
I ̄A=I ̄AB+I ̄AC= 20 75°− 20 195°= 34. 64 45° (4.2.9)
I ̄B=I ̄BA+I ̄BC=− 20 75°+ 20 −45°= 34. 64 −75° (4.2.10)