10.2 SINGLE- AND THREE-PHASE SYSTEMS 459(a) The line current of the motor, before the addition of the capacitor bank, isIM=S 3 φ
√
3 VL=25 , 000
√
3 × 220= 65 .6AAfter the addition, the new value of line current isIcorr=PM
√
3 VLPFcorr=17 , 680
√
3 × 220 × 0. 9= 51 .55A(b) The corrected new value of reactive power isQcorr=PMtan(cos−^10. 9 )= 17 .68 tan 25.8°= 8 .56 kVARThe kVA (kVAR ) rating of the capacitor bank needed to improve the power factor from
0.707 to 0.9 lagging is then found asQcap=Qcorr−QM= 8. 56 − 17. 68 =− 9 .12 kVARThe power triangle is shown in Figure E10.2.1.SM = 25 kVA
Scorr = 19.64
kVA
25.8°45 °PM = 17.68 kWQM = 17.68 kVARQcorr = 8.56 kVARQcap = 9.12 kVA RFigure E10.2.1Power triangle(c) Per-phase capacitive kVAR= 9. 12 / 3 = 3 .04 kVAR. With wye connection,VLN^2
XC=(
220 /√
3) 2XC= 3. 04 × 103orXC=(
220 /√
3) 23. 04 × 103= 5. 31 Hence,C=1
2 π× 60 × 5. 31= 500 μF(d) With delta connection,
VL^2
XC=2202
XC= 3. 04 × 103or