10.2 SINGLE- AND THREE-PHASE SYSTEMS 459
(a) The line current of the motor, before the addition of the capacitor bank, is
IM=
S 3 φ
√
3 VL
=
25 , 000
√
3 × 220
= 65 .6A
After the addition, the new value of line current is
Icorr=
PM
√
3 VLPFcorr
=
17 , 680
√
3 × 220 × 0. 9
= 51 .55A
(b) The corrected new value of reactive power is
Qcorr=PMtan(cos−^10. 9 )= 17 .68 tan 25.8°= 8 .56 kVAR
The kVA (kVAR ) rating of the capacitor bank needed to improve the power factor from
0.707 to 0.9 lagging is then found as
Qcap=Qcorr−QM= 8. 56 − 17. 68 =− 9 .12 kVAR
The power triangle is shown in Figure E10.2.1.
SM = 25 kVA
Scorr = 19.64
kVA
25.8°
45 °
PM = 17.68 kW
QM = 17.68 kVAR
Qcorr = 8.56 kVAR
Qcap = 9.12 kVA R
Figure E10.2.1Power triangle
(c) Per-phase capacitive kVAR= 9. 12 / 3 = 3 .04 kVAR. With wye connection,
VLN^2
XC
=
(
220 /
√
3
) 2
XC
= 3. 04 × 103
or
XC=
(
220 /
√
3
) 2
3. 04 × 103
= 5. 31
Hence,
C=
1
2 π× 60 × 5. 31
= 500 μF
(d) With delta connection,
VL^2
XC
=
2202
XC
= 3. 04 × 103
or