0195136047.pdf

(Joyce) #1

464 AC POWER SYSTEMS


TABLE 10.3.1Load-Bus Data
Quantity Symbol Value

Voltage V 115 kV
Current I 1kA
Apparent power S 220 MVA
Real power P 160 MW
Reactive power Q 120 MVAR
Power factor cosθ 0.8 lagging
Phase angle θ 36.9°
Load impedance Z 66.1
Load resistance R 52.9
Load reactance XL 39.7

TABLE 10.3.2Transmission-Line Data
Quantity Symbol Value

Resistance R 3 
Inductive reactance XL 8 
Series impedance Z 8.5
Series impedance angle θ 69.4°
Real power loss Ploss 9MW
Reactive power loss Qloss 24 MVAR
Voltage drop Vdrop 8.5 kV

TABLE 10.3.3Source-Bus Data

Quantity Load Bus Line Source Bus

Voltage 115 8.5 127.7 kV
Real power 160 9 169 MW
Reactive power 120 24 144 MVAR
Apparent power 200 — 222 MVA
Angle 36.9° — 40.4°

TABLE 10.3.4Load-Bus Data with
Power-Factor Correction
Quantity Symbol Value

Voltage V 115 kV
Current I 0.8 kA
Apparent power S 160 MVA
Real power P 160 MW
Reactive power Q 0MVAR
Power factor cosθ 1
Phase angle θ 0°
Load impedance Z 82.7
Load resistance R 82.7
Load reactance XL 0 
Free download pdf