11.4 TRANSFORMER PERFORMANCE 487Solution(a) The equivalent circuit of the transformer, referred to the high-voltage (primary) side,
neglecting the exciting current of the transformer, is shown below in Figure E11.4.1(a).
Note that the voltage at the load terminals referred to the high-voltage side is 240× 10 =
2400 V. Further, the load current corresponding to the rated (full) load condition is
50 × 103 / 2400 = 20 .8 A, referred to the high-voltage side. With a lagging power factor
of 0.8,I ̄ 1 =I ̄ 2 /a= 20. 8 −cos−^10. 8 = 20. 8 − 36 .9°Using KVL,V ̄ 1 = 2400 0°+( 20. 8 − 36 .9°)( 1. 5 +j 2. 0 )= 2450 0 .34°If there is no load, the load-terminal voltage will be 2450 V. Therefore, from Equation
(11.4.1b),% voltage regulation=V 1 −aV 2
aV 2× 100 =2450 − 2400
2400× 100 = 2 .08%V 1 aV 2 = 2400 ∠^0 ° VI 1 = I 2 /a = 20.8∠−36.9° A
−
+−Load1.5 Ω
Reqj 2.0 Ω
jXeq(a)
Figure E11.4.10.34° aV 2 = 2400 ∠^0 ° Vcos−^1 0.8 = 36.9°I 1 =20.8∠−36.9° A|I 1 Req| = 31.2 VV 1 = 2450 ∠0.34°|j I 1 Xeq| = 41.6 V(b)
VS−
+−V 1I 1 = I 2 /a = 20.8∠−36.9° A
+−aV 2 = 2400 ∠ 0 ° Load0.5 Ω j 2.0 Ω Req = 1.5 Ω j Xev = j2.0 Ω(c)
Feeder