504 MAGNETIC CIRCUITS AND TRANSFORMERS


former to step up voltage from 220 V to 2420
V. Without exceeding the rated current of any
winding, determine the kVA rating of the auto-
transformer, the kVA transformed by transformer
action, and the kVA conducted.

11.6.6A 5-kVA, 480:120-V, two-winding, 60-Hz,
single-phase transformer has an efficiency of
95% while delivering rated load at rated voltage
and 0.8 power factor lagging. This transformer

is to be connected as an autotransformer to step
down a 600-V source to 480 V.
(a) Draw a schematic connection diagram as an
autotransformer.
(b) Find the maximum kVA rating as an auto-
transformer.
(c) Compute the efficiency as an autotrans-
former delivering its rated kVA at 480 V and
0.8 power factor lagging.