HEAT TRANSFER 161
and cross-sectional area for flowD
$/ 4
0. 01482 D 0 .000172 m^2 per tube or:
0. 000172 ð 162 D 0 .0279 m^2 per pass.
∴ G^0 D
37. 5 / 0. 0279 D1346 kg/m^2 s
In equation 9.61:
hið 0. 0148 / 0. 136 D 0. 023
0. 0148 ð 1346 / 0. 00290.^8
1986 ð 0. 0029 / 0. 1360.^4
hiD 0. 211
68690.^8
42. 40.^4 D1110 W/m^2 K
or, based on the outside area,hioD
1110 ð 0. 0148 / 0. 019 D865 W/m^2 K
or: hioD 0 .865 kW/m^2 K.
Overall coefficient
Neglecting the wall and scale resistance, the clean overall coefficient is:
1 /UcD
1 / 1. 02 C
1 / 0. 865 D 2 .136 m^2 K/kW
The area available isAD
324 ð 3. 65 ð$ð 0. 019 D 70 .7m^2 and hence the minimum
value of the design coefficient is:
1 /UDDAm/Q
1 D
420 330 D90 deg K, 2 D
380 295 D85 deg K
and: mD
90 85 /ln
90 / 85 D 87 .5deg K
∴ 1 /UDD
70. 7 ð 87. 5 / 2607 D 2 .37 m^2 K/kW
The maximum allowable scale resistance is then:
RD
1 /UD
1 /Uc D
2. 37 2. 136 D 0 .234 m^2 K/kW
This value is very low as seen from Table 9.16, and the exchanger would not give the
required temperatures without frequent cleaning.
PROBLEM 9.28
A 150 mm internal diameter steam pipe, carrying steam at 444 K, is lagged with 50 mm
of 85% magnesia. What will be the heat loss to the air at 294 K?
Solution
In this case:diD 0 .150 m,doD 0 .168 m anddwD 0. 5
0. 150 C 0. 168 D 0 .159 m.
dsD
0. 168 ð 2 ð 0. 050 D 0 .268 m anddm(the logarithmic mean ofdoandds) D
0 .215 m.