Dave Gerr - Boat Mechanical Systems Handbook-How to Design, Install, and Recognize Proper Systems in Boats

(Rick Simeone) #1
system and the effective net output of air.
Column 3 of Table 16-2 gives the minimum
effective blower system output after allowing
for duct and other system losses.
Example: Assume that After Burner’s
engine vents are fitted with louver grilles at
the outside and with a 90-degree bend in the
water-trap box inside, and then run through
2.5 feet (0.76 m) of duct hose to exhaust from
low in the bilge. Referring back to Table 14-4,
we would find

2.5 feet× 2% per foot= 5%
90-degree bend= 10%
Louver grille= 20%
Total approximate loss= 35%
Effective vent output= 100% – 35%= 65% of
blower’s rated cfm output

If we installed a single 250 cfm blower, the
net blower system output is then

250 cfm× 0.65= 162.5 cfm

or

7 m^3 /min.× 0.65= 4.55 m^3 /min.

Referring to Table 16-2, we find the mini-
mum acceptable blower system output is

Net compartment volume= 290 cu. ft.
(7.89 m^3 )

From column 3 of Table 16-2, we find

Net compartment volume is over 100 cu. ft.
(2.839 m^3 )
Blower system output= Fo=
(0.2× 290 cu. ft.)+ 40 = 98 cfm

or

Blower system output= Fo=
(0.2× 7.89 m^3 )+ 1.13= 2.71 m^3 /min.

Accordingly, the combination of the
250 cfm (7 m^3 /min.) blower we selected with
the louvers and ducting planned should meet
the CFR requirements. The final system out-
put is subject to test measurement on the
actual boat—to prove that the system as in-
stalled really does deliver a minimum of
98 cfm (2.71 m^3 /min.).
Again, if we would install the twin 250 cfm
(7 m^3 /min.) blowers, we would find that un-
der the engine vent sizing rule we would meet
this blower output requirement with ease.

Exhaust Ducts Located
Low Down
Because gasoline vapors are heavier than air
and sink to collect in the bilge, the blower
exhaust ducts must extend down to the
lower third of the compartment volume
(Figure 16-5). In some compartments, this
can pose a problem because the duct can be
so low that the duct intake opening might be

PART FIVE:VENTILATION, AIR-CONDITIONING, AND HEATING


Figure 16-5.
Exhaust ducts for
blowers must
extend down to the
lower third of the
compartment vol-
ume (Courtesy
ABYC)

Free download pdf