Buildings Other Than Dwellings (England and Wales) ~
Notes:
- For display windows separate consideration applies. See
Section 5 in A.D., L2A. - The poorest acceptable thermal transmittance values provide
some flexibility for design, allowing a trade off against other
thermally beneficial features such as energy recovery systems. - The minimum U-value standard is set with regard to minimise
the risk of condensation. - The concept of area weighted values is explained on page 443.
- Elements will normally be expected to have much better
insulation than the limiting U-values. Suitable objectives or
targets could be as shown for domestic buildings.
Further requirements for the building fabric ~
Insulation continuity ~ this requirement is for a fully insulated
external envelope with no air gaps in the fabric. Vulnerable places
are at junctions between elements of construction, e.g. wall to
roof, and around openings such as door and window reveals.
Conformity can be shown by producing evidence in the form of a
report produced for the local authority building control department
by an accredited surveyor. The report must indicate that:
- the approved design specification and construction practice
are to an acceptable standard of conformity, OR - a thermographic survey shows continuity of insulation over
the external envelope. This is essential when it is impractical
to fully inspect the work in progress.
Air tightness ~ requires that there is no air infiltration through
gaps in construction and at the intersection of elements.
Permeability of air is tested by using portable fans of capacity to
suit the building volume. Smoke capsules in conjunction with air
pressurisation will provide a visual indication of air leakage paths.
Element of
construction
Limiting area
weighted ave.
U-value (W/m^2 K)
Limiting individual
component
U-value
Roof 0.25 0.35
Wall 0.35 0.70
Floor 0.25 0.70
Windows, doors, roof-lights,
roof windows and curtain walling
2.20 3.30
High use entrances and roof vents 6.00 6.00
Large and vehicle
access doors
1.50 4.00
Thermal Insulation, Buildings Other Than Dwellings---2