1100 STACK SAMPLING
12 inches (0.3 m) in diameter or 113 in^2 (0.071 m^2 ) cross-
sectional area. Sampling ports must not be within 2 duct
diameters downstream or half a diameter upstream from
any flow disturbance. Sampling points are then determined
by dividing the stack into equal area sections as shown in
Figures 2 and 3. A table is provided in the Method which
gives the percentage of the stack diameter from the inside
wall to each traverse point. For stacks greater than 24 inches
in diameter, no point should be closer than 1 inch from the
wall; for smaller stacks, no closer than 0.5 inch.
Once these criteria are met measurement of the direction
of flow is made to insure absence of significant cyclonic
flow. The angle of the flow is determined by rotating a
Type S pitot tube until a null or zero differential pressure is
observed on the manometer. The angle of the pitot tube with
the stack is then measured. This procedure is repeated for
each sampling point and the average of the absolute values
of the angles calculated. If the average angle is greater
than 20º, the sampling site is not acceptable and a new site
must be chosen, the stack extended, or straightening veins
installed.
A few unusual cases have been accounted for by the
method. If the duct diameter or size is smaller than that
required by Method 1, Method 1A can be used. For cases
where 2 equivalent stack diameters downstream or a half
diameter upstream are not available, a directional velocity
probe can be used to determine the absence of cyclonic flow,
as described in Method 1. If the average angle is less than
20º, then the sampling site is satisfactory; however a greater
number of points must be used.
Test Method 2
Test Method 2 is used to determine the average velocity in a
duct by measuring the differential pressure across a Type S
(Stausscheibe) pitot tube. The Type S pitot tube is preferable
to the standard pitot tube when there are particles that could
cause plugging of the small holes in the standard pitot tube.
Measurement sites for velocity determination are chosen as
described in Method 1, that is, required number of sites and
absence of cyclonic or swirling flow.
The type S and standard pitot tubes are shown in Figure 4.
When the Type S pitot tube has been correctly manufactured
and installed on a probe as shown in Figure 5, there is no
interference and calibration is not necessary. A pitot tube
constant of 0.84 is assumed. If the criteria for interferences
are not met, the method discusses the necessary calibration
procedures.
DUCT DIAMETERS DOWNSTREAM FROM FLOW DISTURBANCE* (DISTANCE B)
(^02)
10
20
30
40
50
0.5 1.0 1.5 2.0 2.5
(^345) 67 8 (^910)
20
24 OR 25a
8 OR 9a
16
12
STACK DIAMETER = 0.30 TO 0.61 m (12-24 in)
STACK DIAMETER > 0.61 m (24in)
FROM POINT OF ANY TYPE OF DISTURBANCE
(BEND, EXPANSION, CONTRACTION, ETC.)
aHIGHER NUMBER IS FOR RECTANGULAR STACKS OR DUCTS
DUCT DIAMETERS UPSTREAM FROM FLOW DISTURBANCE (DISTANCE A)
MINIMUM NUMBER OF TRAVERSE POINTS
DISTURBANCE
MEASUREMENT
SITE
DISTURBANCE
B
A
FIGURE 1 Minimum number of traverse points for particulate traverses.
C019_003_r03.indd 1100C019_003_r03.indd 1100 11/18/2005 11:07:14 AM11/18/2005 11:07:14 AM