498 INDOOR AIR POLLUTION
may be nullifi ed. And with the present concern over air pollu-
tion, failure to disperse the fumes may give rise to legal action
against the building owner.
Fume absorbers such as charcoal have been proposed
to relieve the fume disposal problem, so have air washers
and catalysts. These devices have not been used because
the kinds and amounts of fumes released are constantly
changing in research and are therefore unpredictable.
Despite the number of warnings in the literature, rain
caps, cone shaped covers or hoods fastened to the tops of ver-
tical stacks—are still being used to prevent rain from enter-
ing exhaust stacks. It is important that their use be avoided
completely. There are several simple stack arrangements that
will prevent entry of rain into exhaust stacks when fans are
not operating. One such arrangement is shown in Figure 7.
BUILDING AIR INTAKES
In high-rise research buildings, mechanical equipment is
frequently installed in the penthouse and in the basement.
Because of the possibility of recirculating fumes released from
or near the roof, outdoor air is often taken at the second fl oor
level on the prevailing wind side of the building, and away
from fume exhausts. Assistance in determining the prevailing
wind direction at the building site may be obtained from the
local weather bureau.
BASIC PERFORMANCE CRITERIA
The following may be used as a general guide for the selec-
tion of hood blower systems that will provide optimum
AIR FLOW PATTERNS AROUND A BUILDING
Wake cavity
boundary
Wake boundary
Free stream
Wind direction Building
Peripheral
flow
Cavity
Return flow
FIGURE 6
Very low toxicity level materials
Noxious odours, nuisance dusts and fumes 80 fpm
General lab use
Corrosive materials
Moderate toxicity level materials
(TLV of 10–1000 ppm)
100 fpm
Tracer quantities of radioisotopes
Higher toxicity level materials
(TLV less than 10 ppm)
125–150 fpm
Pathogenic microorganisms
High alpha or beta emitters
Very high toxicity level materials (TLV less than 0.01
ppm)
An enclosed glove box
should be used
average face velocities for various exhaust materials. Tables
listing the TLV for various chemical compounds may be
obtained from the American Conference of Governmental
Industrial Hygienists.
HOW TO CUT AIR CONDITIONING COSTS
As a rule of thumb, each 300 cfm of air exhausted through
hoods requires one ton of refrigeration. Current operating
costs are about 50 to 60 dollars per ton of air conditioning
for a four month period. Installed equipment averages about
$1,000 per ton. So, a hood exhausting at 900 cfm would
require about three tons of air conditioning at a capital expense
of $150 to $180 per season. However, if the same hood had
C009_001_r03.indd 498C009_001_r03.indd 498 11/18/2005 10:29:58 AM11/18/2005 10:29:58 AM