AUTOMATIC VOLTAGE REGULATION 97
Table 4.3. Typical data for AVR control systems
Parameter Low Values
Typical
High
Ga 250 500 1500
Ta 0.01 0.04 0.1
Kf 0.02 0.06 0.1
Tf 1 0.1 0.4 0.6
Tf 2 0.3 1.5 2.5
Vmax 5.0 15.0 20.0
Vmin 0.0 0.0 0.0
Ke 1.0 1.0 1.0
Te 0.05 0.4 1.2
SE 75 0.45 0.75 0.96
SE 100 0.80 0.90 0.96
A 0.07 0.08 0.1
B 0.4 0.5 0.6
Gg 0.30.350.4
Tr 1 0.01 0.02 0.03
Tr 2 0.01 0.02 0.03
Kda 0.03 0.04 0.06
4.2.4 Typical parameter values for AVR systems
Table 4.3 shows typical per unit values for the gains, limits and time constants used in the automatic
voltage regulation systems for generators having ratings up to 50 MW.
Reference
1.Computer representation of excitation systems. IEEE Transactions, PAS 87, No.6, June 1968.