170 HANDBOOK OF ELECTRICAL ENGINEERING
Figure 7.9 Coordination of MCCBs at a distribution board.
Add Zc 2 to Zfcto give the fault impedance Zfdas:-
Zfd=Zfc+Zc 2 = 0. 0143 +j 0. 002759 + 0. 0587 +j 0. 00195
= 0. 073 +j0.00471 ohms
The fault making current Ifdis:-
Ifd=
Vp
Zfd
=
440. 0
1. 732 ( 0. 073 +j 0. 00471 )
= 3473 Arms
Locate the point U for 3473 A on the prospective curve in Figure 7.9.
k) Check the peak making capacity and peak let-through capacity of the MCCBs chosen above.
The following manufacturer’s data are typical for 125 A and 32 A MCCBs:-
MCCB Making capacity Let-through capacity
rating
kArms kApeak
kApeak(cut-off)
Note 1
32 A 95 209 6.0
125 A 132 290 25.0
Note 1: Approximate values of the doubling factor taken to be
2.2.