298 HANDBOOK OF ELECTRICAL ENGINEERING
In order to reduce the total current to 30,000 amps, each generator needs to contribute 6000 amps.
Therefore the following condition must be satisfied,Ifg=E′′I 1
V(X′′d+Xr)=
1. 1 × 1049. 8
1. 0 ×( 0. 15 +Xr)=6000 ampsTransposing gives,
Xr=1. 1 × 1049. 8
1. 0 × 6000
− 0. 15 =0.0425 pub) Case B: Star-connected reactors
From Figure 11.12 it can be seen that the left-hand side and right-hand pairs of generators con-
tribute the same amount of fault current, because the system is symmetrical. The combined
impedance of a pair of generators isX′′d/2. The combined impedance of two pairs of generator
and their shared reactors is,
Zpairs=X′′d
4+
Xr
2The fault current contributed by the four outer generators is,Ifg 4 =E′′I 1
VZpairsThe contribution from the centre generator is 7698.2 as found in a).
The total fault current is again 30,000 amps and is given by,If 5 =E′′I 1
V
[
1
Zpairs+Xr]
+ 7698. 2 = 30000. 0
=
1. 1 × 1049. 8
1. 0
1
0. 15
4
+
Xr
2+Xr
+7698.2 ampsTransposing gives,
Xr=0.00952 puc) Case C: Delta-connected reactors
This case is similar to the star case of b) and the equivalent delta reactance values are simply
three times those of the star reactance values.Hence, Xr=0.02856 pu.It is interesting to note that in this case there will be no current flowing in the reactor
that couples the two outer busbars. However, this reactor cannot be omitted because it serves its
purpose when faults occur at the outer switchboards.d) Comparison of cases
As a rough estimate it may be assumed that the cost of a reactor is directly proportional to its
current rating and its value of reactance.