Protective Relay Coordination


12.1 Introduction to Overcurrent Coordination


Protective devices, usually relays or fuses, are installed at supply points in a power system to accu-
rately detect and quantify a disruptive disturbance in the system. The variable most frequently used
for detection is the supply line current, and in most situations this is detected through the use of
current transformers. Occasionally direct acting devices are used e.g. fuses for voltages up to about
33,000 volts or magnetic elements in low voltage moulded-case circuit breakers (MCCBs).


For special purposes other variables such as voltage, active power, impedance, admittance and
frequency are used.


Most onshore oil production, petrochemical, industrial and offshore platforms use radial power
generation and distribution power systems. These systems will use several voltage levels depending
upon the total power demand and the kW ratings of the largest individual consumers. The transition
from one voltage to the next higher one is influenced mainly by the highest normal load current
that can be handled by conventional circuit breakers, busbar systems within switchgear and power
cables. The ‘highest’ current is typically about 4000 amperes. The maximum fault currents that can
be experienced within a particular power system must also be carefully considered when choosing
the operating voltages. (If in any doubt, then choose a higher voltage because plants are usually
extended or modified, and as such their prospective fault currents tend to increase.)


Figure 12.1 shows a typical hierarchy of switchboards and voltages for a large plant which has
its own gas-turbine power generators (not all the switchboards and individual consumers are shown).
The hierarchy of switchboards, for example, SB-A, SB-B, SB-C and SB-D is a typical situation, and
is one in which overcurrent coordination can occasionally be difficult to achieve for all operating
considerations.


There are two basic operating cases to consider:-

a) Fully loaded power system with all the main generators running. (Usually one is off-line as a
standby, but periodically this generator will need to be put on-line to relieve one of the others.
Hence a major fault could occur during the changeover situation.)

b) Lightly loaded power system with only one generator running. This could be during the start-up
of the production plant. The fault currents throughout the system will be at their lowest levels and
this will tend to cause the fault clearance times to rise, and the coordination margins to increase.