314 HANDBOOK OF ELECTRICAL ENGINEERING



  • Reverse active power (32).

  • Negative phase sequence (46).

  • Stator earth fault current (51 G) and (64).

  • Over terminal voltage, (59) Note 1.

  • Under terminal voltage, (27) Note 1.

  • Overfrequency, (81) Note 2.

  • Underfrequency, (81) Note 2.

  • Winding temperature (26).


Note 1: These can be combined in one voltage relay.


Note 2: These can be combined in one frequency relay.


A typical scheme that contains most of these relays is shown in Figure 12.2.


12.2.2 Overcurrent


12.2.2.1 Response of a generator to a major fault


When a major fault occurs externally from the generator but near to the generator stator terminals or
near its switchgear, two reactions take place:-


Figure 12.2 Protective devices for a high voltage generator.