Handbook of Electrical Engineering

(Romina) #1
HARMONIC VOLTAGES AND CURRENTS 411

The motor running details are,


Running output power 217.8 kW
Running voltage 323.3 volts
Running current 761.1 amps
Running speed 400 rev/min
Running torque 5200 nm
Running input power 246.1 kW

The transformer that feeds the bridge has the following ratings,


Rated kVA 6000
Voltage ratio, volts/volts 11,000/600
Leakage reactance in per-unit 0.04
Leakage reactance at 346 volts/phase 0.0024 ohms

Commutating reactance= 2 × 0. 0024 = 0 .0048 ohms.


For (15.1) the variables and parameters are,

Vd=323.1 volts
E=346.0 volts
Id=761.1 amps
X=0.0048 ohms

Therefore,


323. 1 =

3


6 × 346

π

cosα−

3 × 0. 0048 × 761. 1

π
= 810 .285 cosα− 3. 4886

cosα=

326. 59

810. 29

= 0. 4033

α=66.215 degrees

From (15.2)


323. 1 =

3


6 × 346

2 π

( 0. 4033 +cos( 66. 215 +u))

0. 7975 = 0. 4033 +cos( 66. 215 +u)
u= 66. 215 − 65. 677 =0.538 degrees
=0.00939 radians

From (15.4)


a 1 =cos 66. 215 +cos 66. 753
= 0. 4033 + 0. 3947 = 0. 7980