430 HANDBOOK OF ELECTRICAL ENGINEERING
Table 15.6. Harmonic rms currents and voltages in a star-wound induction motor that is fed from a current
source inverter
Harmonic
number
Stator current Rotor current Magnetising
current
Air-gap voltage
Mag.
(Amps)
Angle
(Degrees)
Mag.
(Amps)
Angle
(Degrees)
Mag.
(Amps)
Angle
(Degrees)
Mag.
(Amps)
Angle
(Degrees)
1 392.28 0 370.54 11.33 78.36 −68.32 229.67 21.68
5 78.45 180.0 75.58 180.014 2.87 179.63 42.06 269.63
7 56.01 180.0 53.99 180.014 2.05 179.63 42.06 269.63
11 35.66 0 34.35 0.007 1.30 −0.186 42.06 89.81
13 30.67 0 29.07 0.007 1.10 −0.186 42.06 89.81
17 23.07 180.0 22.23 180.005 0.84 179.88 42.06 269.88
19 20.65 180.0 19.89 180.005 0.76 179.88 42.06 269.88
23 17.05 0 16.43 0.004 0.62 −0.093 42.06 89.91
25 15.69 0 15.12 0.004 0.57 −0.093 42.06 89.91
29 13.53 180.0 13.03 180.003 0.49 179.93 42.76 269.93
31 12.65 180.0 12.19 180.003 0.46 179.93 42.76 269.93
Figure 15.13 Instantaneous voltages and currents in an induction motor supplied from a current source inverter.