Handbook of Electrical Engineering

(Romina) #1

430 HANDBOOK OF ELECTRICAL ENGINEERING


Table 15.6. Harmonic rms currents and voltages in a star-wound induction motor that is fed from a current
source inverter


Harmonic
number


Stator current Rotor current Magnetising
current

Air-gap voltage

Mag.
(Amps)

Angle
(Degrees)

Mag.
(Amps)

Angle
(Degrees)

Mag.
(Amps)

Angle
(Degrees)

Mag.
(Amps)

Angle
(Degrees)
1 392.28 0 370.54 11.33 78.36 −68.32 229.67 21.68
5 78.45 180.0 75.58 180.014 2.87 179.63 42.06 269.63
7 56.01 180.0 53.99 180.014 2.05 179.63 42.06 269.63
11 35.66 0 34.35 0.007 1.30 −0.186 42.06 89.81
13 30.67 0 29.07 0.007 1.10 −0.186 42.06 89.81
17 23.07 180.0 22.23 180.005 0.84 179.88 42.06 269.88
19 20.65 180.0 19.89 180.005 0.76 179.88 42.06 269.88
23 17.05 0 16.43 0.004 0.62 −0.093 42.06 89.91
25 15.69 0 15.12 0.004 0.57 −0.093 42.06 89.91
29 13.53 180.0 13.03 180.003 0.49 179.93 42.76 269.93
31 12.65 180.0 12.19 180.003 0.46 179.93 42.76 269.93

Figure 15.13 Instantaneous voltages and currents in an induction motor supplied from a current source inverter.