The coefficients of performance of actual and reversible refrigerators
operating between the same temperature limits can be compared as follows:
(6–22)
A similar relation can be obtained for heat pumps by replacing all COPR’s
in Eq. 6–22 by COPHP.
The COP of a reversible refrigerator or heat pump is the maximum theo-
retical value for the specified temperature limits. Actual refrigerators or heat
pumps may approach these values as their designs are improved, but they
can never reach them.
As a final note, the COPs of both the refrigerators and the heat pumps
decrease as TLdecreases. That is, it requires more work to absorb heat from
lower-temperature media. As the temperature of the refrigerated space
approaches zero, the amount of work required to produce a finite amount of
refrigeration approaches infinity and COPRapproaches zero.
COPR•
6 COPR,rev¬¬irreversible refrigerator
COPR,rev¬¬reversible refrigerator
7 COPR,rev¬¬impossible refrigerator
310 | Thermodynamics
EXAMPLE 6–6 A Questionable Claim for a Refrigerator
An inventor claims to have developed a refrigerator that maintains the refrig-
erated space at 35°F while operating in a room where the temperature is
75°F and that has a COP of 13.5. Is this claim reasonable?
Solution An extraordinary claim made for the performance of a refrigerator
is to be evaluated.
Assumptions Steady operating conditions exist.
Analysis The performance of this refrigerator (shown in Fig. 6–52) can be
evaluated by comparing it with a reversible refrigerator operating between
the same temperature limits:
Discussion This is the highest COP a refrigerator can have when absorb-
ing heat from a cool medium at 35°F and rejecting it to a warmer medium at
75°F. Since the COP claimed by the inventor is above this maximum value,
the claim isfalse.
1
175 460 R2> 1 35 460 R 2 1
12.4
COPR,maxCOPR,rev
1
TH>TL 1
EXAMPLE 6–7 Heating a House by a Carnot Heat Pump
A heat pump is to be used to heat a house during the winter, as shown in
Fig. 6–53. The house is to be maintained at 21°C at all times. The house is
estimated to be losing heat at a rate of 135,000 kJ/h when the outside tem-
perature drops to 5°C. Determine the minimum power required to drive
this heat pump.
Cool refrigerated space
at TL = 35°F
Refrigerator
Warm environment
at TH = 75°F
COP = 13.5
FIGURE 6–52
Schematic for Example 6–6.
135,000 kJ/h
Heat loss
House
TH = 21°C
Cold outside air
TL = –5°C
HP
Wnet,in =?
QH
QL
·
·
·
FIGURE 6–53
Schematic for Example 6–7.