EXECUTION


DESCRIPTION E C P



6.1


G E N E R A L 


GENERAL (continued)


6.1.12


W A L L A N C H O R A G E 


CASEWORK WALL ANCHORAGE, except for PENINSULA/ISLAND casework or base casework with
MECHANICAL SPACING ALLOWANCES (because of the need to be engineered on an individual basis),
requires:

6.1.12.1


CONTINUOUS BLOCKING or
BACKING of at least 2” x 6”
(51 mm x 152 mm) nominal
wood or 6” x 16 ga (152 mm x
1.2 mm) sheet metal, installed
by others, shall be appropriately
located in all wood or metal stud
walls.

2X6 flat blocking
by others

6" X 16 ga. cont.
sheet metal
stud by others

6.1.12.2


MANUFACTURER to provide
appropriate blocking or backing
location layouts on their shop
drawings for all tall, base, and
wall-hung casework for both top
and bottom runs of fasteners.

Storage
Cabinet

Wall Cabinet

Base Cabinet

6.1.12.3



ADJACENT cabinet units to be fastened together at the front with a minimum of two #8 x 1-1/4”
(31.7 mm) flat-, oval-, or pan-head screws, a maximum of 30” (762 mm) on center, and:
6.1.12.3.1 Binder-head SEX BOLTS are permitted.
6.1.12.3.2 If COVER CAPS are required, it shall be so specified. M

Section 10 - Casework (Page 48 of 51)