aa
224 Chapter 5 / Transient and Steady-State Response Analyses
Consider the system shown in Figure 5–44(a). The closed-loop transfer function is
given by
The characteristic equation
now has two roots with negative real parts for positive values of J,Kp, and Thus
derivative control introduces a damping effect. A typical response curve c(t)to a unit-
step input is shown in Figure 5–44(b). Clearly, the response curve shows a marked
improvement over the original response curve shown in Figure 5–46(b).
Proportional-Plus-Derivative Control of Second-Order Systems. A compromise
between acceptable transient-response behavior and acceptable steady-state behavior may
be achieved by use of proportional-plus-derivative control action.
Consider the system shown in Figure 5–45. The closed-loop transfer function is
The steady-state error for a unit-ramp input is
The characteristic equation is
Js^2 +AB+KdBs+Kp= 0
ess=
B
Kp
C(s)
R(s)
=
Kp+Kd s
Js^2 +AB+KdBs+Kp
Td.
Js^2 +Kp Td s+Kp= 0
C(s)
R(s)
=
KpA 1 +Td sB
Js^2 +Kp Td s+Kp
+–
R(s) C(s)
Kp+Kds s(Js^1 +B)
Figure 5–44
(a) Proportional-plus-derivative control of a system with inertia load; (b) response to a unit-step input.
R(s) C(s)
(a) (b)
Kp(1+Tds)
c(t)
1
(^0) t
1
Js^2
+–
Figure 5–45
Control system.
Openmirrors.com