582 Chapter 8 / PID Controllers and Modified PID ControllersOutputc(t)t (sec)Unit-Step Response of Compensated System
1.41.210.80.60.40.20
02468101214Figure 8–17
Unit-step response
curve.Unit-Ramp Input and Outputc(t)t (sec)Unit-Ramp Response of Compensated System
20181614121086420
02468101214161820Compensated SystemFigure 8–18
Unit-ramp input and
the output curve.The resulting unit-step response curve is shown in Figure 8–17 and the unit-
ramp response curve in Figure 8–18. Notice that the closed-loop pole at s=0.1897
and the zero at s=0.2 produce a long tail of small amplitude in the unit-step
response.
For an additional example of design of a PID controller based on the frequency-
response approach, see Problem A–8–7.