590 Chapter 8 / PID Controllers and Modified PID Controllers8–5 Modifications of PID Control Schemes
Consider the basic PID control system shown in Figure 8–25(a), where the system is sub-
jected to disturbances and noises. Figure 8–25(b) is a modified block diagram of the same
system. In the basic PID control system such as the one shown in Figure 8–25(b), if the ref-
erence input is a step function, then, because of the presence of the derivative term in the
control action, the manipulated variable u(t)will involve an impulse function (delta func-
tion). In an actual PID controller, instead of the pure derivative term , we employ
where the value ofgis somewhere around 0.1. Therefore, when the reference input is a
step function, the manipulated variable u(t)will not involve an impulse function, but will
involve a sharp pulse function. Such a phenomenon is called set-point kick.
PI-D Control. To avoid the set-point kick phenomenon, we may wish to operate
the derivative action only in the feedback path so that differentiation occurs only on
the feedback signal and not on the reference signal. The control scheme arranged in this
way is called the PI-D control. Figure 8–26 shows a PI-D-controlled system.
From Figure 8–26, it can be seen that the manipulated signal U(s)is given by
U(s)=Kpa 1 +
1
Ti s
bR(s)-Kpa 1 +
1
Ti s
+Td sbB(s)
Td s
1 +gTd s
Td s
PID
controllerPlant
Gp(s)1
Tis1TdsOutput
Y(s)Noise
N(s)Reference
inputR(s)(a)(b)Disturbance
D(s)Gp(s)Y(s)N(s)R(s) E(s)B(s)Observed signal B(s)U(s)D(s)Kp++++++
++
++
+ ++Figure 8–25
(a) PID-controlled
system;
(b) equivalent block
diagram.Openmirrors.com