however, lines are generally 10 miles or less. Short-circuit levels at the substation are dependent on
voltage level and substation size. The average short-circuit level at a distribution substation has been
shown, by survey, to be about 10,000 A. Feeder load current levels can be as high as 600 A but rarely
exceed about 400 A with many never exceeding a couple of hundred amperes.
23.1.2 Fault Levels
There are two types of faults, low impedance and high impedance. A high impedance fault is considered
to be a fault that has a highZdue to the contact of the conductor to the earth, i.e.,Zfis high. By this
definition, a bolted fault at the end of a feeder is still classified as a low impedance fault. A summary of
findings on faults and their effects is as follows.
S
R
138 kV Distribution
Substation Transformer
ISC = 10,000 A 13.8 kV
Feeder Breaker
Peak Load = 600 A Three-Phase, 4-Wire,
Multi-grounded Fuse Cutout
Normally Open Tie Switch
Single-Phase Sectionalizer
Distribution
Transformers
4–15 Holmes/ Transformer
Fixed Capacitor Bank
Three-Phase Recloser
Switched Capacitor
Bank (= 600 kVAR)
Pothead
Faulted Circuit Indicator
Elbow Disconnect
Normally Open Tie
Normally Open Tie
Underground Lateral
FCI FCI
FIGURE 23.1 Typical distribution system.