Handbook of Civil Engineering Calculations

(singke) #1

kips/lin in. Use a^5 /i6-in (7.9-mm) weld, which has a capacity of 3 kips/lin in (525.4
N/mm). Then F
2
=f
2
+/ 2
2
= 130,300/L
4



  • 1029/Z
    2
    < 3
    2


. This equation is satisfied by L =
14 in (355.6 mm).
5. Determine the thickness of the stiffener plate
Assume this plate is triangular (Fig. %d). The critical section for bending is assumed to co-
incide with the throat of the plate, and the maximum bending stress may be obtained by
applying/= (P/tWsin^2 O)(I + 6e'IW), where e' = distance from center of seat to center of
bearing.
Using an allowable stress of 22,000 lb/in^2 (151.7 MPa), we have e' = e-2.5 = 0.31 in
(7.9 mm), t= {77/[22 x 5(14/14,87)^2 ]}(1 + 6 x 0.31/5) = 1.08 in (27.4 mm).
Use a I
1
Xs-In (28.6-mm) stiffener plate. The shearing stress in the plate caused by the
weld is v = 2(3000)71.125 = 5330 < 14,500 lb/in
2
(99.9 MPa), which is acceptable.


DESIGN OFA WELDED


MOMENT CONNECTION


A Wl 6 x 40 beam frames to the flange of a W12 x 72 column and transmits a shear of 42
kips (186.8 kN) and a moment of 1520 in-kips (171.1 kN-m). Design a welded connec-
tion, using E60 electrodes.

Calculation Procedure:


  1. Record the relevant properties of the two sections
    In designing a welded moment connection, it is assumed for simplicity that the beam
    flanges alone resist the bending moment. Consequently, the beam transmits three forces
    to the column: the tensile force in the top flange, the compressive force in the bottom
    flange, and the vertical load. Although the connection is designed ostensibly on an elastic
    design basis, it is necessary to consider its
    behavior at ultimate load, since a plastic
    hinge would form at this joint. The con-
    nection is shown in Fig. 9.
    Record the relevant properties of the
    sections: for the W16 x 40, d = 16.00 in
    (406.4 mm); b = 7.00 in (177.8 mm); tf =
    0.503 in (12.8 mm); tw = 0.307 in (7.8
    mm); Af = 7.00(0.503) - 3.52 in^2 (22.7
    cm^2 ). For the W12 x 72, k= 1.25 in (31.8
    mm); ^ = 0.671 in (17.04 mm); tw - 0.403
    in (10.2 mm).
    2. Investigate the need for
    column stiffeners: design the
    stiffeners if they are needed
    The forces in the beam flanges introduce
    two potential modes of failure: crippling
    of the column web caused by the com-
    pressive force, and fracture of the weld
    transmitting the tensile force as a result of
    FIGURE 9. Welded moment connection. the bending of the column flange. The

Free download pdf