Architectural and Engineering Design Standards

(avery) #1
SECTION 07550

MODIFIED BITUMEN MEMBRANE ROOFING (SBS)

Modified Bitumen Membrane Roofing (SBS)
UIHC #20X-0XX 07550-6

C. The Contractor shall provide to the Owner a notarized written warranty assuring that all
roofing work including caulking, flashing, and sheet metal to be watertight for a period of two
years from the date of final acceptance of the work. Warranty shall include all materials and
workmanship required to repair any leaks that develop as a result of the work.

PART 2 PRODUCTS


2.01 MODIFIED BITUMEN SHEET ROOFING


A. SBS Modified Bitumen Roofing and Flashing Membranes


  1. Acceptable Manufacturers and Products


a. The Garland Company, Inc.

1) Base Sheet: HPR Torchable Base Sheet

2) Finish Ply Sheet: StressPly IV Mineral

3) Stripping Ply/Base Flashing: HPR Torchable Base Sheet

4) Flashing Membrane: StressPly IV Mineral

b. Siplast, Inc.

1) Base Sheet: Paradiene 20 HT TG

2) Finish Ply Sheet: Parapdiene 30 HT FR TG

3) Stripping Ply/Base Flashing: Paradine 20 TG

4) Flashing Membrane: Veral Aluminum

c. Product Performance Minimums: Roof systems must equal or exceed all
performance minimums and maximums listed for all products and
performance characteristics.

1) Base Sheet (Base Ply)

Application Method Torch Applied
Nominal thickness 110 mil (3.0 mm)
Net Coverage 100 sq/ft (9.29 m²)
Compound SBS Modified Asphalt
Reinforcement Fibrous Glass Mat or
Scrim
Top Surface Fine Sand
Bottom Surface Polypropylene or

November 1, 2016
Free download pdf