Drawing Number
1.4Single Door - Level 3 - StrikeDate:UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011CVJob NumberSerial Number Drawn ByProject
DocumentsRevisionsDrawing Type
Card Access DetailsNoneSafety & Security Card Access StandardsCeilingStructure48 in AFFTo Card Access Panel½ in flex raceway w/string.
¾ in conduit raceway w/string.6inRDRLCKDSMDevice Rough In RequirementsJBDevice Description Opening
F
UPIR / ALM FS1in conduit sleeve into JB from
unsecured side of door
SJB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSideRDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSideUDSM ½ flex raceway from J-Box into the wall down to a ¾ in opening in frame. 6 in from end of door. Coordinate the location on frame and drilling with the GC. F FrameLCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F FramePIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.Typical Application : Telecom Room, Department Access, Med RoomsNovember 1, 2016