Drawing Number
1.13Double Door - Level 2 - Mag LockDate:UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011CVJob NumberSerial Number Drawn ByProject
DocumentsRevisionsDrawing Type
Card Access DetailsNoneSafety & Security Card Access Standards1in conduit sleeve into JB from
unsecured side of doorCeilingStructure48 in AFFJ
BoxTo Card Access Panel¾ in EMT Raceway with pull string
½ in Flex Raceway with pull stringPIR / ALMDSMTo Video SystemDSMPTELCKKS
Located on secured
side of door
Located on public
side of doorDevice Rough In Requirements
Device Description Opening
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide
S UF F F FSSKEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
PTE ¾ conduit raceway from the ceiling to the PTE location. Provide 4sq box in wall with 1G mud ring vertical. S SecuredSideLCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F FrameDSMS UDoor can be Single or Double Egress.
Coordinate with SSC and GC on Device locations.DSM Use PIR / ALM raceway to PIR / ALM Box. Provide a pull wire from this box location to each DSM switch. F Frame
PIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.LCKNote:
1 If door is double egress, the leaf exiting the secured space
does not require a LCK or PTE if no pull hardware is
provided.Note 1Note 1November 1, 2016