Drawing Number
1.19
Software House iStar 16 Reader Access Panel Layout
Date:
UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011
CV
Job Number
Serial Number Drawn By
Project
Documents
Revisions
Drawing Type
Card Access Details
None
Safety & Security Card Access Standards
PS-1
Power
Supply
Software
House
iStar
Control Panel
16 Readers
PS-nnn
Expansion
Modules
Panel
24wx36h
Max 48 inches
AFF 78 inches
By Others (Electrical Contractor),
120Vac Emergency Power, Dedicated Circuit(s)
Network IP Connection (Minimum Wire Runs 2)By Others (Network provider), DropNet F.A.
PS-1
Power
(Expansion)Supply
Software House Rough In Requirements
Device Description
Fire
Alarm
Fire Alarm contractor to provide a NC contact at the panel for the SSC contractor to
connect to the lock power supplies to drop in event of a fire alarm. This will provide Magnetic Lock interuption.
Network
Drop Provide Network wire run for connection to panel. 10/100 connection on SecNet
120V
EmergencyPower Provide 120 VAC Emergency Power dedicated to this equipment
By Others (Fire Alarm System),
Mag Lock Interuption Connection
Notes:
1 Fire Alarm contractor to test mag lock power interuption
during testing
PS-1
Power
Supply
November 1, 2016