Drawing Number
1.19Software House iStar 16 Reader Access Panel LayoutDate:UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011CVJob NumberSerial Number Drawn ByProject
DocumentsRevisionsDrawing Type
Card Access DetailsNoneSafety & Security Card Access StandardsPS-1Power
SupplySoftware
House
iStar
Control Panel
16 ReadersPS-nnnExpansion
Modules
Panel
24wx36hMax 48 inchesAFF 78 inchesBy Others (Electrical Contractor),
120Vac Emergency Power, Dedicated Circuit(s)
Network IP Connection (Minimum Wire Runs 2)By Others (Network provider), DropNet F.A.PS-1Power
(Expansion)SupplySoftware House Rough In Requirements
Device DescriptionFire
AlarmFire Alarm contractor to provide a NC contact at the panel for the SSC contractor to
connect to the lock power supplies to drop in event of a fire alarm. This will provide Magnetic Lock interuption.Network
Drop Provide Network wire run for connection to panel. 10/100 connection on SecNet120V
EmergencyPower Provide 120 VAC Emergency Power dedicated to this equipmentBy Others (Fire Alarm System),
Mag Lock Interuption ConnectionNotes:
1 Fire Alarm contractor to test mag lock power interuption
during testingPS-1Power
SupplyNovember 1, 2016