12.5 Electric Motors 361
TABLE 12.3 Examples of Motors used in Different Applications
Electrical Power
Requirements
Load Motor Type Starting Ability Starting Current Size hp Phase Voltage
Type (1) (Torque) (2) (3) (4) (5) (6)
Shaded-pole Very low Low .035 –.2 kW Single Usually 120
induction 1/2 to 1 times (1/20 –1/4 hp)
running torque
Split-phase Low High .035 –.56 kW Single Usually 120
Easy
1 to 1 times 6 to 8 times (1/20 – 3/4 hp)
Starting
running torque running current
Loads Permanent-split, Very low Low .035 –.8 kW Single Single voltage
capacitor- 1/2 to 1 times (1/20 –1 hp) 120 or 240
induction running torque
Soft-start Very low Low 5.6 – 25 kW Single 240
1/2 to 1 times 2 to 2 times (7 –50 hp)
running torque running current
Capacitor-start, High Medium .14 – 8 kW Single 120 – 240
induction-run 3 to 4 times 3 to 6 times (1/6 –10 hp)
running torque running current
Repulsion-start, High Low .14 –16 kW Single 120 – 240
induction-run 4 times 2 to 3 times (1/6 – 20 hp)
running torque running current
Difficult Capacitor-start, High Medium .4 – 20 kW Single 120 – 240
Starting capacitor-run 3 to 4 times 3 to 5 times (1/2 – 25 hp)
Loads running torque running current
Repulsion-start, High Low .8 –12 kW Single Usually 240
capacitor-run 4 times 2 to 3 times (1–15 hp)
running torque running current
Three-phase, Medium High .4 – 300 kW Three 120 – 240;
general-purpose 2 to 3 times 3 to 6 times (1/2 – 400 hp) 240 – 480
running torque running current or higher
1
2
1
2
1
2
1
2
1
2
1
2
1
2
R
Split-phase
R
Repulsion-start induction Capacitor-start
Centrifugal
switch R
Repulsion-induction Capacitor-motor
Schematic Diagrams for AC Motors
Source:From Electric Motors, Fifth Edition, 1982. Copyright © 1982 AAVIM. Reprinted by permission.
Continued
Copyright 2010 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s).