Saia-Burgess Controls AG
Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Communication interfaces4
PCD7.F1504.5.5 RS 485 with PCD7.F150, Port #1 (without PCD1.M110)
PCD7.F150:
RS 485 electrically isolated, with line
termination resistors capable of activation, for
socket A
The electrical isolation is achieved with 3
optocouplers and a DC / DC transducer.
The data signals are protected against
surges by a suppressor diode (10 V). The
line termination resistors can be connect-
ed / disconnected with a jumper.10
11
12
13
14
15
16
17
18
19J1OPEN CLOSED
1918171614131211PCD7.F150Socket A RX - TX
/RX - /TXRX - TX
Bus RS 485 /RX - /TXD
/DS-BUSPGNDPGNDPGND50 VDC50 VDCSGND (electrically isolated, must
be connected to the cables shield)Block diagram:TXDRXDRTS75176OPTO-0601SGND+5VE330 Ohm150 Ohm330 OhmD/D+5V
PGND SGND+5VEENSGNDTransmitReceive RS 485DriverDCDCNot all manufacturers use the same connection configuration, so the data lines may
need to be crossed.The potential difference between PGND and the data lines Rx-Tx, Rx- / Tx (and
SGND) is limited to 50 V by a suppressor capacitor.For installation details, see manual 26 / 740 :
“Installation components for RS 485 networks”.