Saia-Burgess Controls AG
Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Communication interfaces
4
PCD7.F150
4.5.5 RS 485 with PCD7.F150, Port #1 (without PCD1.M110)
PCD7.F150:
RS 485 electrically isolated, with line
termination resistors capable of activation, for
socket A
The electrical isolation is achieved with 3
optocouplers and a DC / DC transducer.
The data signals are protected against
surges by a suppressor diode (10 V). The
line termination resistors can be connect-
ed / disconnected with a jumper.
10
11
12
13
14
15
16
17
18
19
J1
OPEN CLOSED
19
18
17
16
14
13
12
11
PCD7.F150
Socket A RX - TX
/RX - /TX
RX - TX
Bus RS 485 /RX - /TX
D
/D
S-BUS
PGNDPGND
PGND
50 VDC
50 VDC
SGND (electrically isolated, must
be connected to the cables shield)
Block diagram:
TXD
RXD
RTS
75176
OPTO-0601
SGND
+5VE
330 Ohm
150 Ohm
330 Ohm
D
/D
+5V
PGND SGND
+5VE
EN
SGND
Transmit
Receive RS 485Driver
DC
DC
Not all manufacturers use the same connection configuration, so the data lines may
need to be crossed.
The potential difference between PGND and the data lines Rx-Tx, Rx- / Tx (and
SGND) is limited to 50 V by a suppressor capacitor.
For installation details, see manual 26 / 740 :
“Installation components for RS 485 networks”.