Saia-Burgess Controls AG
Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Communication interfaces4
RS 422 with PCD2.F520Connection diagram for RS 485 line termination resistors+5 V/RX-/TXRX-TXPCD1.M1xx
PCD2.Mxx0PCD1.M1xx
PCD2.Mxx0PCD1.M1xx
PCD2.Mxx0
+5 V37/
47/n36/
46n n /n/nnPCD2.Mxxx
socket B(1), B2Pull up
330 OhmPull down
330 Ohm Segment lenght max. 1200 m
max. 32 stationsTermination
Resistor
150 OhmAt the first and last stations, jumper J1 must be set to the “CLOSED“ position.
At all other stations, jumper J1 must be set to “OPEN” (factory setting)For installation details, see manual 26 / 740 “Installation components for RS 485“Installation components for RS 485Installation components for RS 485
networks””The PCD7.F772 Profibus module (details in 4.8.3) and the PCD7.F802 LON module
(details in 4.9) also have an RS 485 interface.
However, these modules are not supported by all PCD1 / PCD2 units.
The wiring is identical to the RS 485 wiring for the PCD2.F520 Modules.4.6.2 RS 422 with PCD2.F520
RS 422: socket B(1) Port #339
38
37
36
35
34
33
32
31
30PGNDTX/TXRX/RXSGNDTX/TXRX/RXJ1OPEN CLOSED39
38
37
3634
33
32
31PCD2.F520Port # 2RS232Port # 3RS 422Peripheral CableScrew
terminal block,
socket B/B1 Socket B(1)