Hardware Manual

(John Hannent) #1

Saia-Burgess Controls AG


Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Communication interfaces

4


RS 232 with PCD2.F520/F522

4.6.3 RS 232 with PCD2.F520/F522RS 232 with PCD2.F520 / F522


PCD2.F520:
1 x RS 232 with RTS / CTS and
1 x RS 485 electrically connected
or
1 x RS 232 with RTS / CTS and
1 x RS 422 without RTS / CTS
for socket B / B1 / B2
not suitable for modem

PCD2.F522:


choice between
2 × RS 232 with RTS / CTS
or
1 × RS 232 full with RTS / CTS,
DTR / DSR, DCD
Jumper for
2 x RS 232 or
1 x RS 232 full
suitable for modem connection for
socket B / B1 / B

The PCD2.F520 and PCD2.F522 modules are only supported by
PCD2.M120 / M150 / M170 / M480 controllers.

RS 232: socket B(1), Port #2, for peripheral device

39
38
37
36
35
34
33
32
31
PGND 30

TXD

RXD

RTS

CTS

SGND

TXD

RXD

RTS

CTS

39
38
37
36

34
33
32
31

Port # 3

Port # 2RS 232

PCD2.F520 or
PCD2.F522 in the mode 2 x RS 232

PCD2.M170/M480


Screw
terminal block,
socket B/B1

Peripheral Cable
Free download pdf