Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.E165/166Input/output (I/O) modules5
For every 2 inputs, a 3-colour LED is fitted:Colour E0 E1 E2 E3 E4 E5 E6 E7 E8 E9 E10 E11 E12 E13 E14 E15
off L L L L L L L L L L L L L L L L
red H L H L H L H L H L H L H L H L
green L H L H L H L H L H L H L H L H
yellow H H H H H H H H H H H H H H H HInput circuits and terminal designation
Depending on external wiring, this module may be used for source or sink operation.
Source operation (positive logic):E 1 E 010 k 10 k10 k 10 kLED redLED greenUe 24 VDCL L Screwless terminalsIf both inputs 0 and 1 are
switched on, the yellow (orange)
LED lights upSwitch closed (+ at input): signal state "H", LED lights up
Switch open: signal state "L", LED offSink operation (negative logic):E 1 E 0Ue 24 VDCL L Screwless terminalsSwitch closed (- at input): signal state "L", LED off
Switch open: signal state "H", LED lights upWatchdog: This module can interact with the watchdog; if it is used on base address
240 (or 496 for the PCD2.M17x), the last input with address 255 (or 511 for the
PCD2.M17x) cannot be used.
For details, please refer to the “Watchdog” section, which describes the correct use of
the watchdog in conjunction with PCD2 components.