Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.A200Input/output (I/O) modules5
LEDs and connection terminalsBus connectorBus interfaceRelaysContact protectionLEDsScrew terminalsRelay contacts
Supply 24 VDC for^
Relay coils9 8 7 6 5 4 3 2 1 0
A 3 A 2 A 1 A 0A 3 A 2 A 1 A 0Output circuits and terminal designationA09 8 1 0
A37 6I/O Bus
PCD Bus
Contact
protection
Relay
contactsTerminals24 VDC Isolated contactsAdress
LED A3Relay energized (contact closed): LED on
Relay reset (contact open): LED off
24 VDC must be connected to the +/- terminals.
With an open relay contact, the current leakage through the contact protection is
0.7 mA (at 230 V / 50 Hz). This should be taken into account for smaller AC loads.
If this is too high, it is recommended to use a PCD2.A220 Module (without contact
protection).Watchdog: This module can be used on all base addresses; there is no interaction with the
watchdog on the CPUs. For details, please refer to the “Watchdog” section, which describes
the correct use of the watchdog in conjunction with PCD2 components.LED Output
0 A0
1 A1
2 A2
3 A3