PCD2.W3x0

Input/output (I/O) modules

5


5.7.4 PCD2.W3x0, analogue inputs, 8 channels, 12 bit resolution


Application
High-speed input module for general use with 8 channels, each with 12 bit resolution.
Different variants for voltage 0 ... 10 V, current 0 ... 20 mA and the use of different
resistance thermometers are available.
Module overview resolution *)

PCD2.W300: Voltage 0 ... 10 V 2.442 mV
PCD2.W310: Current 0 ... 20 mA20 mA 4.8844.884 �A�A�AA
PCD2.W340: General purpose module
0 ... 10 V 2.442 mV
0 ... 20 mA 4.884 �A�AA
Pt/Ni 1000 (default)
Pt 1000: -50 ... +400 °C 0.14 ... 0.24 °C
Ni 1000: -50 ... +200 °C+200 °C 0.09...0.12 °C0.09 ... 0.12 °C
PCD2.W350: Temperature sensor
Pt/Ni 100
Pt 100: -50 ... +600 °C 0.14...0.20 °C0.14...0.20 °C0.14 ... 0.20 °C
Ni 100: -50 ... +250 °C+250 °C 0.06...0.12 °C0.06 ... 0.12 °C
PCD2.W360: Temperature sensor
Pt 1000 -50 ... +150 °C 0.07 ... 0.09 °C (resolution < 0.1 °C)
Method of linearization for temperature inputs: by software
*) Resolution = value of least significant bit (LSB)
Technical data

Input ranges: see module overview
Galvanic separation: no
Resolution (digital representation): 12 bits (0 ... 4095)
Measuring principle: non-differential, single-ended
Input resistance: W300: 20 k�� / 0.15 %
W310: 125 �� / 0.1 %
W340: U: 200 k�� / I: 125 ��
W350: not relevant
W360: not relevant
Maximum signal current for the
resistance thermometers:

2.0 mA

Accuracy at 25 °C W300, 310: ± 0.5 %
W340, 350, 360: ± 0.3 %
Repeating accuracy: ± 0.05 %
Temperature error (0 ... +55 °C)± 0.2 %
Conversion time A/D: < 10 μsμs
Overvoltage protection: W340: ± 50 VDC (permanent)
W300 *): + 50 VDC (permanent)
Overcurrent protection: W340: ± 40 mA (permanent)
W310 *): + 40 mA (permanent)
EMC protection: yes