Hardware Manual

(John Hannent) #1

Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Saia-Burgess Controls AG


PCD2.W3x0

Input/output (I/O) modules

5


Formulae for temperature measurement
For Ni 1000 (PCD2.W340)
Validity: Temperature range - 50 ... + 210 °C
Computational error: ± 0.5 °C

T= - 188.5 +


260 • DV


(^2616)


- 4.676 • 10 -6 • (DV - 2784)^2


For Pt 1000 (PCD2.W340)
Validity: Temperature range - 50 ... +400 °C
Computational error: ± 1.5 °C

T= - 366.5 +


450 • DV


2474 + 18.291 •^10


-6 • (DV - 2821) 2


Resistance measurement up to 2.5 kΩ (PCD2.W340)
Special temperature sensors or any other resistances up to 2.5 k�� can be connected
to the PCD2.W340. The digital value can be calculated as follows:

DV=


16 380 • R


(7 500 + R)


where 0 ≤ DV ≤ 4095 and R=the resistance to be measured in ��.

For Ni 100 (PCD2.W350)
Validity: Temperature range - 50 ... +250 °C
Computational error: ± 1.65 °C

T= - 28.7 +


300 • DV


(^3628)


- 7.294 • 10 -6 • (DV - 1850)^2


For Pt 100 (PCD2.W350)
Validity: Temperature range - 50 ... +600 °C
Computational error: ± 1 °C

T= - 99.9 +


650 • DV


3910 + 6.625 •^10


-6 • (DV -2114) 2


For Pt 1000 (PCD2.W360)
Validity: Temperature range - 50 ... +150 °C
Computational error: ± 0.25 °C

T= - 178.1 +


200 • DV


2509 + 3.873 •^10


-6 • (DV -2786) 2


T = temperature
DV = digital value