Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W3x0
Input/output (I/O) modules
5
Formulae for temperature measurement
For Ni 1000 (PCD2.W340)
Validity: Temperature range - 50 ... + 210 °C
Computational error: ± 0.5 °C
T= - 188.5 +
260 • DV
(^2616)
- 4.676 • 10 -6 • (DV - 2784)^2
For Pt 1000 (PCD2.W340)
Validity: Temperature range - 50 ... +400 °C
Computational error: ± 1.5 °C
T= - 366.5 +
450 • DV
2474 + 18.291 •^10
-6 • (DV - 2821) 2
Resistance measurement up to 2.5 kΩ (PCD2.W340)
Special temperature sensors or any other resistances up to 2.5 k�� can be connected
to the PCD2.W340. The digital value can be calculated as follows:
DV=
16 380 • R
(7 500 + R)
where 0 ≤ DV ≤ 4095 and R=the resistance to be measured in ��.
For Ni 100 (PCD2.W350)
Validity: Temperature range - 50 ... +250 °C
Computational error: ± 1.65 °C
T= - 28.7 +
300 • DV
(^3628)
- 7.294 • 10 -6 • (DV - 1850)^2
For Pt 100 (PCD2.W350)
Validity: Temperature range - 50 ... +600 °C
Computational error: ± 1 °C
T= - 99.9 +
650 • DV
3910 + 6.625 •^10
-6 • (DV -2114) 2
For Pt 1000 (PCD2.W360)
Validity: Temperature range - 50 ... +150 °C
Computational error: ± 0.25 °C
T= - 178.1 +
200 • DV
2509 + 3.873 •^10
-6 • (DV -2786) 2
T = temperature
DV = digital value