Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W3x5
Input/output (I/O) modules
5
Terminals
Digital/analogue values
Input signals and type Digital values
PCD2.W305 PCD2.W315 PCD2.W325 Classic xx7 Simatic
+ 10.0 V + 20 mA +10 V 4095 4095 27684
+ 5.0 V + 10 mA 0 V 2047 2047 13842
0 V 0 mA -10 V 0 0 0
Connection concept for voltage and current inputs
The voltage and current input signals are connected directly to the 14-pole terminal
block (E0 ... E6 and COM). To minimize the amount of interference coupled into the
module via the transmission lines, connection should be made according to the
principle explained below.