Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
MountingCPUs and expansion housings3
3.5 MountingThe PCD1 and PCD2 can be snapped onto two 35 mm top-hat rails (DIN 50 022).
The PCD1/PCD2 can also be screwed to any other flat surface with 4 M4 screws; the
grooves provided for this purpose can be accessed by lifting off the snap-on cover.
Mounting the PCD1/PCD2 on the top-hat rail Press bottom of housing onto the mounting
surface
Press upwards against the top-hat rail
Press top of housing against the mounting
surface and snap into place
Push the housing down onto the top-hat rail to
ensure that it is secure
Removal
To remove the housing, push upwards and pull out.3.5.1 Mounting position and ambient temperatureA vertical surface is normally used to mount the module holder; the I/O connections
to the modules then also run vertically. In this mounting position, the ambient
temperature may be from 0 °C to 55 °C. In all other positions, air convection works
less well, and an ambient temperature of 40 °C should not be exceeded.