Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
Expansion housings and bus cables
CPUs and expansion housings
3
When selecting I/O cassettes, ensure that the internal 5 V and +V supply is not
overloaded.
Detailed information on planning combined PCD2/PCD3 systems can be found in the
PCD3 manual 26/789.
3.6.3 Expansion with PCD4 components
Starting from a PCD2.M120/M150/M170/M480, the PCD4.C225 coupling bus module
makes it possible to run the following I/O modules and manual control modules from
the PCD4 series:
Digital input/output modules Manual control modules
PCD4.E11x PCD4.A810
PCD4.E60 PCD4.A820
PCD4.A200
PCD4.A250
PCD4.A350
PCD4.A400
PCD4.A410
PCD4.B90x
Any PCD4 I/O modules not listed are not supported.
As shown in the illustration below, the PCD4.C225 is connected to the PCD2 via a
PCD2.K100/K110/K120 extension cable.
Using standard PCD4.C220 or PCD4.C260 bus modules, up to 6 additional module
sockets can be attached to the right-hand side of the PCD4.C225 coupling bus
module (making a total of 8 PCD4 sockets).
It is necessary to ensure that the internal 5 V and +V supply for the PCD2 is not
overloaded. The power consumption for the PCD4 modules can be found in manual
26/734.
PCD2.M120/M150/M170/M480
PCD4.C225 PCD4.C220/C260
PCD2.K1xx