Power supply and connection plan
CPUs and expansion housings
3
3.9.2 Earthing and connection plan
Ground wire plan with earthing bar
PGU
24 VDC
Battery
WD
Run
Halt
Error
CPU
Supply
0V +24VDC
1.5 mm^2 1.5 mm (^2)
Exxx Axxx
Wxxx
Earthing bar
_
_
++
- Shielding and
grounding plate
1.5 mm^2 / max. 25cm
In the bottom part of the PCD1/PCD2 housing there is a shielding and earthing
plate. This constitutes the common, large-area ground for all I/O modules and for the
external power supply.
When a module is plugged in at the I/O level, the blades on this plate ensure a
reliable multi-point contact to the relevant module.
The zero-potential (Minus pole) of the 24 V supply is connected to the Minus
terminal of the PCD1/PCD2 supply. This should be connected to the earthing bar
with the shortest possible wire (< 25 cm) of 1.5 mm^2. The same applies to the Minus
connection to the F1xx or the interrupt terminal.
Any shielding of analogue signals or communication cables should also be brought to
the same earth potential, either via a Minus terminal or via the earthing bar.
All Minus connections are linked internally. For problem-free operation, these
connections should be reinforced externally with short wires of 1.5 mmly with short wires of 1.5 mm^2.