Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
Interrupt inputsCPUs and expansion housings3
Interrupt
inputXOB called in case of a
positive edgeInput where the relevant XOB
is not programmed
IN0 XOB 20 I 8100
IN1 XOB 21 I 8101
IN2 XOB 22 I 8102
IN3 XOB 23 I 81034 k 710 k4 k 7IN2
IN1LIN30 1 2 3 4 5 6 7 8
IN09PGND
Input signals (source operation): PGND
H = 15.. 30 V
L = -30.. + 5 V or no connectedInput signals (sink operation):
H = 15 .. 30 V or no connected
L = -30.. + 5 Vsource operation
(for sink operation
L at +24 V)3.3 nFμC
CF 5407
OUT4
OUT5i
Outputs OUT4 and OUT5 can be used as “normal”, short-circuit-proof transistor
outputs with addresses O 8104 and O 8105, and each loaded up to 0.5 A.
Where the OUT4/OUT5 outputs are used, the + connection (terminal 6) must have a
+24 V supply.