Hardware Manual

(John Hannent) #1

Saia-Burgess Controls AG


Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Communication interfaces

4


Serial interface on Port#0

4.4 Onboard interfaces


4.4.1 PGU connection (PORT # 0, PCD1 and PCD2) (RS 232) for connecting
programming devices


The PGU interface (Port # 0) is connected to a 9-pole D-Sub connector (female). The
interface is used to connect the programming device when the unit is comissioned.
The interface is of type RS 232c.
The pin configuration and associated signals are:

Pin Designation Meaning
1 DCD Data Carrier Detected The equipment signals to the computer that
it recognizes data on the line
2 RXD Receive Data Line for the receiving of data
3 TXD Transmit Data Line for outgoing (sent) data
4 n.c. Not Connected Not used
5 SGN Signal Ground Signal mass. Signal voltages are measured
against this line
6 DSR PGU Connected Recognition PGU. Attached equipment sig-
nals to the computer that it is operational, if
logical unity on this line lies close
7 RTS Request To Send Transmitters switch on. „send request“ (if
this line on logically unity stands, would like
to send the equipment data
8 CTS Clear To Send Ready-to-transmit-state. If this line stands
on logically “high”, the equipment can
receive data
9 +5 V Supply P100 Supply for the programming unit P100

The PGU protocol is provided for operation with a programming device. The use
of the PCD8.P800 service unit is supported from firmware version $301 for all
PCD1 / PCD2 controllers.

PCD8.K111 connecting cable
(P8 and S-Bus protocol, suitable for all PCD1 / PCD2 units)

2

1

4

3

6

5

8

7

9

2

1

4

3

6

5

8

7

9

SGN
DSR

SGN

TX

RX

RTS
CTS CTS

RTS

TX

RX

DTR
PC PCD

D-SUB 9 pol.
(female)

D-SUB 9 pol.
(male)