Saia-Burgess Controls AG
Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Communication interfaces4
Profi S-Net on PCD2.M4804.4.7 Profi S-Net on PCD2.M480
The PCD2.M480 is equipped with a Profi S-Net interface as standard. This can be
used both for programming and for communication with other CPUs (that support
Profi S-Bus) and / or Saia RIOs.Technical details:
Transmission rates up to 1.5 MBit / s
Number of stations up to 124 stations in segments of 32 stations each
Protocols Profi S-Bus, Profi S-IO, DP Slave, HTTP in preparation
(multi-protocol operation on the same interface)Connection diagramOption
B1S-Net
MPIPCD2.M480
B1 B2COM
PGUPort #10 D-Sub
PinProfibus DP
MasterS-Net1 -
2 -
3 RxD / TxD-P
4 RTS / CNTR-P
5 GND
6 +5 V
7 -
8 RxD / TxD-N
9 -For details of the configuration and programming of Profi S-Net functions, please
consult the specialised manuals.