3.1 SINUSOIDAL STEADY-STATE PHASOR ANALYSIS 117
φ
ωC
1
VR = R I
VR + VL + VC = V VL + VC = j(ωL − ) I
I = I ∠ 0 ° (Reference)
(b)
Figure E3.1.6Continued
I V
−
+
(c)
R
GR =^1
IR IL IC
ωL
jB^1
L^ =^ j(− ) jBC^ =^ jωC
φ
ωL
1
IR = V/R
IR + IL + IC = I IC + IL = j(ωC − ) V
V = V ∠ 0 ° (Reference)
(d)
EXAMPLE 3.1.7
Two single-phase 60-Hz sinusoidal-source generators (with negligible internal impedances) are
supplying to a common load of 10 kW at 0.8 power factor lagging. The impedance of the feeder
connecting the generatorG 1 to the load is 1. 4 +j 1. 6 , whereas that of the feeder connecting
the generatorG 2 to the load is 0. 8 +j 1. 0 . If the generatorG 1 , operating at a terminal voltage
of 462 V (rms), supplies 5 kW at 0.8 power factor lagging, determine:
(a) The voltage at the load terminals;
(b) The terminal voltage of generatorG 2 ; and
(c) The real power and the reactive power output of the generatorG 2.
Solution
(a) From Equation (3.1.37) applied toG 1 , 462I 1 ( 0. 8 )= 5 × 103 ,orI 1 = 13 .53 A. WithV ̄ 1
taken as reference, the phasor expression forI ̄ 1 is given byI ̄ 1 = 13. 53 −cos−^10. 8 =
13. 53 − 36 .9° A, sinceG 1 supplies at 0.8 lagging power factor.
The KVL equation yields
V ̄L= 462 0°−( 13. 53 − 36 .9°)( 1. 4 +j 1. 6 )= 433. 8 − 0 .78° V
The magnitude of the voltage at the load terminals is 433.8 V (rms).